Metal zinc oxide arrester is one of the key equipment of power equipment, the leakage current flowing through the arrester is an important index to measure the insulation degree of the arrester. The JCQ-485 series arrester on-line monitoring device can realize real-time monitoring of the insulation condition of the arrester through real-time on-line monitoring of the full current, resistive current, lightning strike times and lightning strike time of the arrester. At the same time, the potential failure of the metal zinc oxide arrester can be found in time by analyzing the monitoring data, which provides an important maintenance basis for the condition-based maintenance. According to the needs of the field, this product is designed for the remote meter type and sensor type two specifications.

Category: Product Center

Key words: equipment


Product Description

1. Arrester online monitoring system
Metal zinc oxide arrester is one of the key equipment of power equipment, the leakage current flowing through the arrester is an important index to measure the insulation degree of the arrester.
The JCQ-485 series arrester on-line monitoring device can realize real-time monitoring of the insulation condition of the arrester through real-time on-line monitoring of the full current, resistive current, lightning strike times and lightning strike time of the arrester. At the same time, the potential failure of the metal zinc oxide arrester can be found in time by analyzing the monitoring data, which provides an important maintenance basis for the condition-based maintenance. According to the needs of the field, this product is designed for the remote meter type and sensor type two specifications.

2. Product model and technical parameters

 

2.1.1 Remote meter type lightning arrester monitoring device

Monitoring Wiring Diagram of Remote Meter Type Lightning Arrester

Remote meter type product model and technical parameters

Picture

Model

Function and technical parameters

Cast aluminum remote meter

JCQ-485 Series

Function: monitor full current, discharge times, discharge time;

RS485The remote transmission circuit adopts photoelectric isolation technology, which has a long transmission distance and strong anti-interference ability;

The round precision cast aluminum shell, good sealing performance, beautiful appearance, good corrosion resistance and electromagnetic shielding effect;

Milliammeter range:220kVand below0-3mA;220kVAbove0-6mA;

Measurement accuracy: ±0.05mA;

Counting range(Cyclable count):0~999(Counting range can be determined as needed);

Protection class:IP68;For outdoor, good waterproof performance;

Nominal discharge current(Ka):10;

Residual voltage at nominal discharge current(KV): ≤1.83;

2mssquare wave tolerance(A):1000(3mATable);2000(6mATable);

4/10usLarge current withstand capability(Ka):100;

Minimum action current(8/20us)(A):50;

Working power supply:DC24V.

Steel shell remote meter

Applicable to indoorGISLightning arrester. Function and technical parameters with cast aluminum meter.

Passive Wireless Lightning Arrester Remote Meter

Device without external power supply, no cable laying, simple construction;

The device is battery-powered, no charging is required, and the continuous battery life is greater6year;

Device data upload time5min/times;

Device AdoptionLoraWireless communication, long transmission distance, using the national network standard wireless communication protocol, strong compatibility.

Lightning arrester monitoring IED

LHRX1908-IED

Working power supply:AC220V±15%,50Hz;

Full current, lightning number and lightning time can be displayed locally;

SupportModbuscommunication protocol,61850 ( DL/T860)Communication Protocol(Optional);

Maximum supported access361 surge arrester meter;

has2a power port,2A light mouth.

 

 

2.1.2 Sensor-type lightning arrester monitoring device

Monitoring Wiring Diagram of Sensor Type Lightning Arrester

Configuration of Sensor Type Lightning Arrester Monitoring System 

Picture

Model

Function and technical parameters

JCQ-485

Each phase arrester needs to be installed1Lightning arrester monitoring device;

Full current effective value:100µA~650mA;

Measurement accuracy: ±(Standard reading ×1 0µA);

Resistive current fundamental peak:10µA~650mA;

Measurement accuracy: ±(Standard reading ×1 0µA);

Protection class:IP66;

Communication mode:RS485,61850(DL/T860)Communication Protocol(Optional).

LHRX1908-IED
Size: Standard 2U Chassis ( 482.5*88*250mm)

Working power supply:AC220V±15%,50Hz;

1Voltage levels require at least1station monitoringIED;

SupportModbuscommunication protocol,61850(DL/T860)Communication Protocol(Optional).

Lhjcq-pt

Size: Standard 2U Chassis ( 482.5*88*250mm)

Working power supply:AC220V±15%,50Hz;

One busbar voltage monitoring device is installed for each section of busbar;

Applicable voltage level range of busbar monitoring device:35kV~1000kV;

Bus voltage measurement range:35V~100V;

Measurement accuracy: ±(Standard reading ×0.5%);

harmonic voltage measurement range:3,5,7,9 times, measurement accuracy ±2%;

System frequency measurement range:45~65HzMeasurement accuracy ±0.01Hz.

 