The GIS partial discharge on-line monitoring system consists of three parts: ultra high frequency (UHF) sensor, signal acquisition device, partial discharge monitoring IED communication unit and monitoring system server. Multiple partial discharge IEDs can form a distributed monitoring system, and multiple devices can be monitored on-line at the same time. The local data processing in the monitoring system is used to process and digitize the signals obtained by the partial discharge monitoring IED, the computer of the server is used to screen, analyze and complete the functions of the local discharge signal, such as recording the value of the local discharge pulse and monitoring the development of the local discharge volume.

Category: Product Center

Key words: equipment


Product Description

1. Product introduction
LHJF1000 GISThe partial discharge on-line monitoring and fault location system consists of the local discharge monitoring IED host, UHF local discharge sensor and expert analysis software. When online monitoring IED is used for networking, a set of monitoring server cabinet will be configured, and high-performance industrial control computer, display, keyboard, mouse, UPS power supply, switch and expert analysis software will be installed inside. The GIL/GIS partial discharge signal is monitored on-line in real time, and the measured data is analyzed, processed and comprehensively judged, the insulation state evaluation report of the equipment is given in real time, and the maintenance plan is arranged according to the monitoring results, so as to avoid major power grid accidents caused by equipment failure and ensure the normal operation of the system with the lowest maintenance cost. ZKA series partial discharge UHF sensor is divided into built-in and external two kinds.

Technical parameters of partial discharge monitoring sensor

Products

Indicator Type

Indicator Name

Index value

Unit

Remarks

 

 

 

 

 

 

 

GIL/GISBureau

Partial discharge monitoring sensor

Environmental indicators

Working temperature

-25 ~ 65

℃

 

Working humidity

< 95%

/

 

 

 

 

comprehensive monitoring performance

Measurement sensitivity

-80 (built-in);

-75 (external);

dbm

 

Measure bandwidth

300 ~2000

MHz

 

Measurement accuracy

0.1

dB

 

Average Equivalent Height

> 10

mm

Test Report of China Electric Power Research Institute

Overvoltage protection

Have

 

 

Signal Interface

N type RF terminal

/

 

 

 

Comprehensive appearance performance

Material

6061Aluminum alloy (built-in)

304Stainless steel (external type)

/

 

Overall dimensions (built-in)

Multiple size options

mm

Support customization

Waterproof performance

Good

 

 

Design life

> 50

Year

 

Applicable voltage level

Full voltage level

/

 

 

Technical parameters of on-line monitoring IED

Products

Indicator Type

Indicator Name

Index value

Unit

Remarks

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GIL/GISBureau

On-line monitoring of partial dischargeIED

 

Working power supply and environment

Power Input

AC 120 ~240

V

 

Power consumption

< 30

W

 

Working temperature

-25~ 65

℃

 

Working humidity

<95%

/

 

 

 

 

 

 

 

 

 

 

 

 

 

comprehensive monitoring performance

Self-test function

Have

/

POST

Access sensor

Built-in, external

/

 

Monitoring bandwidth

300 ~1500

MHz

 

Measurement range

-80~-20

dBm

 

Measurement accuracy

0.1

dB

 

Monitoring sensitivity

-80

dbm

 

Monitoring channel

4 ~16

Road

 

synchronous scanning channel

All channels

/

 

Sample Rate

≥ 100

MHz

 

Refresh Rate

≤ 1

s

 

Sampling mode

24huninterrupted

/

 

Sample Time Override

100%

 

 

Discharge type identification

5More than one typical discharge type

 

 

Monitoring content

discharge amplitude(Q)Phase(Φ)Number of times(N),

discharge rate

 

/

 

LOC Fault Location

Support

/

 

Synchronous signal

Power supply or other

/

 

Noise elimination capability

very strong

/

 

Over-voltage protection

Support

/

 

Signal input interface

NType RF terminal

/

 

Communication Interface

RJ45Optical fiberSCorST

/

 

 

 

system comprehensive performance

Cabinet form

2U/19Inch box-type aluminum profile chassis;

Outdoor hanging box type (304stainless steel);

 

 

Design life

20

Year

 

Applicable voltage level

Full voltage level

/

 

Extended Performance

Maximum Access1000a point

/

Adopt distributed networking

 

Test conditions

EMCTest

By(Highest level)

/

Test Report of China Electric Power Research Institute

System Performance Test

By

/


 

Submit Message

* Note: Please be sure to fill in the information accurately and keep the communication unblocked. We will get in touch with you as soon as possible.